午夜影院免费看_欲妇荡岳丰满少妇岳91白洁_秋霞网av_夜夜骑天天干_欧美三级午夜理伦_亚洲天堂2024

1. Explosion-proof electrical equipment knowledge

(1) Hazardous Locations: According to the provisions of GB3836.14-2000 "Electrical Equipment for Explosive Gas Environments Part 14: Classification of Hazardous Locations", hazardous locations can be divided into Zone 0, Zone 1, Zone 2.

    (a) Zone 0: Sites where explosive gas atmospheres occur continuously or for a long period of time.

    (b) Zone 1: Locations where explosive gas atmospheres may occur during normal operation.

    (c) Zone 2: In normal operation, it is not possible to have an explosive atmosphere, and if it does occur, it occurs occasionally and only for a short period of time.

 (2) Category: The type of electrical equipment is related to the use environment. There are mainly two categories:

     Category I: Coal mining electrical equipment.

     Category II: Other explosive gas atmospheres other than coal mines.

    Type II flameproof type "d" electrical equipment according to the maximum experimental safety gap, intrinsically safe "i" electrical equipment according to the minimum ignition current is divided into IIA, IIB, IIC category (IIB category the most widely used, only hydrogen Sites such as acetylene are required to use Class IIC, see Table 3).

 (3) Maximum surface temperature: The highest temperature of any part or surface that can cause ignition of the surrounding explosive atmosphere when the electrical equipment is operated under the most unfavorable conditions within the permissible range.

 (4) Ignition temperature: The minimum temperature at which a combustible gas or mixture of steam and air is ignited by a hot surface under specified conditions (see Table 1).

(5) Temperature group: The group of electrical equipment divided by its maximum surface temperature (see Table 1).

 Table 1 Relationship between temperature group, surface temperature and ignition temperature

Electrical equipment temperature group

The maximum surface temperature of electrical equipment

Gas or vapor ignition temperature

T1

450℃

>450℃

T2

300℃

>300℃

T3

200℃

>200℃

T4

135℃

>135℃

T5

100℃

>100℃

T6

85℃

>85℃

(6) Dust explosion hazardous locations: According to the frequency and duration of the explosive or flammable dust environment, dust explosion hazardous locations are divided into:

Zone 10: Zones in which explosion or explosion of dust clouds or dust layers that may occur or may occur during normal processing, treatment or cleaning.

Zone 11: Sites not designated as Zone 10, but under unusual conditions, areas where dust clouds or dust layers mixed with air can reach explosive concentrations can occur.

(7) The relationship among dust temperature group, ignition temperature, and maximum surface temperature (Table 2).

Table 2

 

Temperature group

Lighting temperature T

Highest surface temperature

No overload

With approved overload

T11

T>270℃

215℃

190℃

T12

<200℃T≤270℃

160℃

145℃

T13

<150℃T≤200℃

120℃

110℃

(8) Examples of flammable gases that are allowed in the use environment:

table 3


Group temperature

category


T1

T2

T3

T4

ⅡA、ⅡB、ⅡC

Methane, ethane, propane, styrene, benzene, toluene, xylene, acetone, carbon monoxide, phenol, cresol, dichloroethylene, chlorobenzene, ammonia, propyne, acrylonitrile, hydrogen cyanide, coke oven gas, hydrogen Wait

Butane, cyclopentane, propylene, ethylbenzene, isopropylbenzene, methanol, ethanol, propanol, butanol, cyclohexanone, methyl formate, ethyl acetate, dichloroethane, vinyl chloride, methylamine, Ethylene, acetylene, etc. 

Pentane, hexane, cyclohexane, turpentine, naphtha, petroleum, kerosene, fuel oil, gasoline, pentanol, hexanol, chlorobutane, dimethyl ether, crotonaldehyde, etc.

Ethyl methyl ether, acetaldehyde, dibutyl ether, diethyl ether

  

Note: This table is quoted from Appendix B of GB3836.1—2000 “Electrical Equipment for Explosive Gas Environments Part 1: General Requirements”.

Explosion-proof electrical equipment selection principle

2.1 GB3836.15-2000 "Electrical Equipment for Explosive Gas Atmospheres Part 15: Electrical Installations for Hazardous Locations (Excluding Coal Mines)" provides three selection principles for explosion-proof electrical equipment:

(1) According to the classified hazardous area selection, it can be divided into 0 zone, 1 zone, and 2 zone equipment.

Zone 10 equipment: A single intrinsic safety "ia" class. Explosion-proof electrical appliances with other explosion-proof types cannot be used in zone 0.

21 zone equipment: Meet the requirements of one or more types of explosion-proof type such as explosion-proof "d", encapsulated "m", intrinsically safe "i", oil-impregnated "o", and increased safety "e" equipment.

32-zone equipment: Equipment for zones 0 and 1 and electrical equipment of type "n" and special type "s" according to IEC 6007-15.

(2) Select the ignition temperature based on the gas or vapor

Electrical equipment shall be sized for the highest surface temperature of any gas or vapour at the ignition temperature (Table 1)

(3) Selection according to gas type

The type of gas should be considered in the electrical equipment with explosion-proof “d” and intrinsically safe “i”, and the gas category and the electrical category should be in accordance with Table 4.

Table 4 Relationship between gas/vapor classification and equipment category

Gas/Vapor classification

Equipment classification

ⅡA

ⅡA、ⅡB or ⅡC

ⅡB

ⅡB、ⅡC

ⅡC

ⅡC

COPYRIGHT @ ALLRIGHTS RESERVED.

KNEXCN (Original KNEX) ALL EIGHTS RESERVED

主站蜘蛛池模板: 素人fc2av清纯18岁 | 99热免费精品 | 手机毛片在线观看 | 老爷们的床奴np高h 好色婷婷 | 天堂在线观看av | 99极品视频 | 免费成人av片 | 国产免费99 | 免费在线国产视频 | 色呦呦中文字幕 | 久热只有精品 | 亚洲精品大片 | 欧美一级精品 | 青娱乐超碰在线 | 久草免费在线观看视频 | 日韩成人区 | 久久久久久久久久国产 | 久久精品国产免费 | 亚洲在线视频观看 | 国产成人区 | 成人免费毛片糖心 | 大地资源在线资源 | 国产黄色免费大片 | 97麻豆视频 | 午夜合集 | 成人av资源 | 国产人人看 | 日韩欧美久久 | 九九热九九热 | 天天爽天天做 | 黄色网址| 欧美午夜精品一区二区 | 午夜天堂| 国产一区色 | 欧美日韩视频在线 | 国产精品mm | 欧美在线资源 | 日本黄色大片免费看 | 精品午夜一区二区三区在线观看 | 国产网站黄色 | 日韩三级一区二区三区 |